Functional Testing for Condensers and Cooling Towers
Functional Testing Field Tips – Cooling Towers
Key Commissioning Test Requirements
Functional Testing Field Tips – DX Condensers
Key Commissioning Test Requirements
Testing Guidance and Sample Test Forms
This module of the Functional Testing Guide describes the benefits and the process of testing condensers and integrating their operation into the chilled water system. This condenser module highlights key functional testing issues for both cooling towers and direct expansion condensers. Although the emphasis of this module is on functional testing, it describes other related activities such as verification checklists (also referred to as pre-functional tests) that are a precursor to functional testing.
Cooling tower condenser systems are designed to reject heat from the medium (usually water) used to condense refrigerant gas in either an open-circuit or closed-circuit configuration. A brief description of each technology is provided below.
· Open-circuit cooling tower. In an open-circuit cooling tower system, the water used to condense the refrigerant gas is exposed to the atmosphere (hence the term “open-circuit”) as it is distributed across the fill of the cooling tower, collected in the sump, and circulated back through the chiller condenser bundle. The water temperature delivered back to the condenser bundle(s) is controlled by the amount of fill the water is exposed to and the modulation of air flow across the fill. This is probably the most common condenser system used in conjunction with chillers in a commercial HVAC application.
· Closed-circuit cooling tower. A closed-circuit cooling tower is similar to an open-circuit cooling tower, except that the condenser water is circulated through coils within the cooling tower rather than exposing the water to the atmosphere. A combination of spraying water onto the coils, and air flow across them, removes heat from the condenser water by both convection and evaporation. The condenser water temperature is controlled by spraying water onto the coils first and then modulating air flow across the coils. Many closed-circuit cooling towers also have a separate section where the spray water is cooled back down by cascading across fill material and being exposed to air flow (same process as an open-circuit cooling tower). The spray water is collected in the sump and pumped back to the top of the unit. Closed-circuit cooling towers are generally associated with water-loop heat pump systems, but can also be applied to chiller systems.
Direct expansion (DX) condenser systems are designed to condense the refrigerant gas directly – the unit may be either air-cooled or evaporative-cooled. A brief description of each technology is provided below.
· Direct expansion air-cooled. In a direct expansion air-cooled condenser, the refrigerant gas flows through the condenser coils and air is blown across the coils to condense the refrigerant. This is a purely convective heat transfer process. Capacity control is typically based on condenser fan modulation (such as staging ON/OFF, 2-speed motor, and VFD), as well as possibly varying the number of condenser coils filled with refrigerant at any given time (condenser splitting). Although air-cooled condensers are more typically associated with large refrigeration systems, they can also be applied to chillers serving commercial HVAC systems.
· Direct expansion evaporative-cooled units. A direct expansion evaporative-cooled condenser is similar to a closed-loop cooling tower. In this application, heat is removed from the refrigerant by both convection and evaporation heat transfer processes. Capacity control is typically achieved by spraying water onto the coils first before modulating the condenser fan(s). The water spray may be eliminated during winter months to prevent freezing of the condenser. Although evaporative-cooled condensers are more typically associated with large refrigeration systems, they can also be applied to chillers serving commercial HVAC systems.
There are other sections of the Functional Test Guide that will be helpful in integration of the condenser system, as well. Refer to Functional Testing Basics for guidance related to all functional testing activities, regardless of the component or system being tested. Additional integration guidance may be found by referencing the Pumping module and the Chiller module, especially in the context of how the condenser system should integrate with the chiller and condenser pumps.
Key Commissioning Test Requirements lists practical considerations for functional testing. Key Preparations and Cautions address potential problems that may occur during functional testing and ways to prevent them.
Key Commissioning Test Requirements lists practical considerations for functional testing. Key Preparations and Cautions address potential problems that may occur during functional testing and ways to prevent them.
This testing guidance describes the steps and potential issues that may arise during functional testing. Since commissioning providers typically have their own style of forms, the Test Guidance is not provided in a field-ready form. Commissioning providers may use the Test Guidance to expand and improve upon their existing forms. Example tests based on the Test Guidance documents are provided where available.
| Test ID |
Testing Guidance (View Appendix D for Test Descriptions) |
Source (View Appendix E for Source Details) |
Example tests |
|---|---|---|---|
|
TG03 |
STAC/PECI |
Hot Water System Pump Test (Test ID 1009) Chilled Water System Pump Test (Test ID 1010) Condenser Water System Pump Test (Test ID 1011) |
|
|
TG10 |
STAC/PECI |
|
|
|
TG16 |
Writing a Functional Test (general guidance) |
STAC/PECI |
Blank Test Form for Writing a Functional Test (Test ID 1015) Example for Writing a Functional Test (Test ID 1020) |
This table lists publicly-available sample tests from a variety of authors. Some of the tests are written for a specific building, while others are written for a general case. This list of sample test forms also includes the Example Tests listed in the Testing Guidance table above.
| Test ID |
Test Forms (View Appendix D for Test Descriptions) |
Source (View Appendix E for Source Details) |
|---|---|---|
| Condenser System Prefunctional Checklists | ||
|
273 |
Condenser Water Piping Prefunctional Checklist |
DOE/PECI |
|
275 |
Documenting Requirements for Chiller System Startup and Initial Checkout (Example) |
DOE/PECI |
| Condenser System Prefunctional Checklists and Functional Test Procedures | ||
|
362 |
CoolTools/PG&E/Taylor |
|
|
89 |
Multnomah/Kaplan |
|
| Condenser System Functional Test Procedures | ||
|
295 |
DOE/PECI |
|
|
296 |
DOE/PECI |
|
| Component-level Prefunctional Checklists & Functional Test Procedures | ||
|
78 |
Cooling Tower Prefunctional Checklist |
Multnomah/Kaplan |
|
272 |
DOE/PECI |
|
|
1009 |
PECI |
|
|
1010 |
PECI |
|
|
1011 |
PECI |
|